EXCEPTIONS: 1. When approved by the Superintendent of Building, the existing clearance between existing floor joists or girders and existing grade below the floor need not comply with U.B.C. Section 2317.3. This exception shall not be permitted when buildings are relocated on new foundations.
2. When approved by the Superintendent of Building, and when designed by an engineer or architect, partial perimeter foundations may be used in lieu of a continuous perimeter foundation.
9204.3.3 New perimeter Foundations Sill plates for new perimeter foundations shall be anchored as required by Section 91.1806.6.
9204.4 Cripple Wall Bracing.
9204.4.1 General. Exterior cripple walls, not exceeding four feet (1219mm) in height, shall use the prescriptive bracing method listed below. Cripple walls more than four feet (1219 mm) in height require analysis by an engineer or architect in accordance with U.B.C. Section 1601.
9204.4.1.1 Sheathing Requirements. Wood structural panel sheathing shall be not less than 15/32-inch (12 mm) thick. When used, plywood panels shall be constructed of five or more plies. All wood structural panels shall be nailed with 8d common nails spaced four inches (102 mm) on center at all edges and at 12 inches (305 mm) on center at each intermediate support with not less than two nails for each stud. Nails shall be driven so that their head or crown is flush with the surface of the sheathing and shall penetrate the supporting member a minimum of 1½ inch (38 mm). When a nail fractures the surface, it shall be left in place and not counted as part of the required nailing. A new 8d nail shall be located within two inches (51 mm) of the discounted nail and hand driven flush with the sheathing surface.
EXCEPTION: No. 6 x 1½ inch (38 mm) wood screws may be used for sheathing nailing when bracing materials are installed on the interior face of studs and cement plaster or other brittle finished are on the exterior of the sheathed wall.
All horizontal joints must occur over nominal two-inch by four-inch (51 mm by 102 mm) blocking installed with the nominal four-inch (102 mm) dimension against the face of the plywood. All vertical joints must occur over studs. Vertical joints at adjoining pieces of wood structural panels shall be centered on existing studs such that there is a minimum 1/8 inch (3.2 mm) between the panels. Nails shall be placed a minimum of ½ inch (12.7 mm) from the edges of the existing stud. When such edge distance cannot be maintained because of the width of the existing stud, a new stud shall be added adjacent to the existing and connected with 16d common nails at eight inches (206 mm) on center. A minimum of three such nails shall be provided.
9204.4.2 Distribution and Amount of Bracing. See Table 92-A for the distribution and amount of bracing required. Bracing for a building with three or more floor levels above cripple wall studs exceeding 14 inches (356 mm) in height must be designed in accordance with Division 16 of this code.
The braced panel must be at least two times the height of the cripple stud wall but not less than 48 inches (1219 mm) in width. All panels along a wall shall be nearly equal in length and shall be nearly equally spaced along the length of the wall. Braced panels at ends of walls shall be located as near the end as possible.
Where physical obstructions such as fireplaces, plumbing or heating ducts interfere with the placement of cripple wall bracing, the bracing shall then be placed as close to the obstruction as possible. The total amount of bracing required shall not be reduced because of obstructions but the required length of bracing need not exceed the length of the wall.
Underfloor ventilation openings shall be maintained in accordance with U.B.C. Section 2317.7. Braced panels may include underfloor ventilation openings when the height of the solid portion of the panel meets or 75 percent of the height of the cripple stud wall. When the minimum amount of bracing prescribed in Table 92-A cannot be installed due to obstructions along any wall, the bracing must be designed by an architect or engineer in accordance with Section 91.9201.3.
9204.4.3 Stud Space Ventilation. When bracing materials are installed on the interior face of studs forming an enclosed space between the new bracing and existing exterior finish, each braced stud space must be ventilated. Adequate ventilation and access for future inspection shall be provided by drilling one two-inch to three-inch (51 mm to 76 mm) diameter round hole through the sheathing nearly centered between each stud at the top and bottom of the cripple wall. Such holes should be spaced a minimum of one-inch (25 mm) clear from the sill or top plates. In stud spaces containing sill bolts, the hole shall be located on the center line of the sill bolt but not closer than one-inch (25 mm) clear from the nailing edge of the sheathing.
When existing blocking occurs within the stud space, additional ventilation holes shall be placed above and below the blocking or the existing block shall be removed and a new nominal two-inch (51 mm) by four-inch (102 mm) block installed with the nominal four-inch (102 mm) dimension against the face of the plywood. For stud heights less than 18 inches (457 mm) only one ventilation hole need be provided.
9204.4.4 Existing Underfloor Ventilation. Existing underfloor ventilation shall not be reduced without providing equivalent new ventilation as close to the existing as possible. New sheathing may be installed around existing vent openings in braced panels when the length of the panel is increased a distance equal to the length of the vent opening or one stud space minimum.
EXCEPTION: For residential buildings with a post and pier foundation system where a new continuous perimeter foundation system is being installed, ventilation shall be provided in accordance with this Code.